Motorstarter
NOLTA motor starters offer optimum motor protection through:
Thermal over-stressing protection
- No over-stressing of engine and cables
Magnetic high-speed circuit breaker
- Quick and save disconnection in case of short circuit
Integration in plug
- Saves costs since no extra space is required
- Higher flexibility
Rotary field check, phase inverter and equipment-on indicator
- Protection from incorrect engine torque direction
Automatic or manual control
- Connections for floats or control conduit
- Automatic restart
High resistance to short-circuits
(only at thermal-electromagnetic release)
- No back-up fuse necessary
(see datasheet: To Icc = 50 kA)
NOLTA – motor protection starters for one and three phase electrical motors – cost efficient due to high flexibility in application and configuration.
- Thermo-magnetic motor protection
- On/off switch
- Robust polycarbonate housing
- Combination with IEC or CEE plug con

Nominal motors currents of three-phase-motors
(standard values for cage rotors)
The standard values are for nominal internal and surface cooled three-phase-motors with 1500rpm.
Power | 230V | 400V | 500V | Power |
(kw) | A | A | A | (PS) |
0,25 | 1,30 | 0,80 | 0,60 | 0,33 |
0,37 | 2,10 | 1,20 | 0,90 | 0,50 |
0,55 | 2,70 | 1,60 | 1,20 | 0,75 |
0,80 | 3,60 | 2,10 | 1,55 | 1,10 |
1,10 | 4,70 | 2,70 | 2,00 | 1,50 |
1,50 | 6,00 | 3,40 | 2,70 | 2,00 |
2,20 | 8,50 | 4,90 | 3,70 | 3,00 |
3,00 | 11,00 | 6,40 | 4,90 | 4,00 |
4,00 | 15,00 | 8,60 | 6,50 | 5,50 |
5,50 | 20,00 | 11,50 | 8,70 | 7,50 |
7,40 | 26,00 | 15,00 | 11,50 | 10,00 |
11,00 | 39,00 | 22,50 | 17,00 | 15,00 |